+7 (34141) 5-88-33 
Request a callback

Basic heat exchangers

Basic heat exchangersк

Basic heat exchangers

Application

Basic heat exchangers are designed as completing units for central air conditioners with air capacity from 10,000 to 25,000 m3/h. 
Heat carrier is hot (superheated) water according to GOST 20955-75 at temperature not more than 180ºC and pressure not more than 1.2 MPa.

Implement in moderate climate regions, allocation category 3 according to GOST 15150-69.

Show Hide

Models of coils

  • General purpose coil of carbon steel
  • Corrosion proof coil (K) of stainless steel 
Show Hide

Reliability targets

  • average life time not less than 9 years
  • full design service time nit less than11000 hours
  • full no-failure operating time not less than 3000 hours
  • average restoration time not more than 12 hours 

Design

Heat exchangers are multipass accordingly internal het carrier. So they can be four-, six- or eight passes depending on piped grid size.  After movement is achieved by baffle plates.

Heaters must not be installed on units with external vibration with quadratic mean more than 2mm/sec. In winter start should with heat increase not more than 30ºС per hour. Heaters can be welded or jointed through flanges to heat supply system.